Installation and Mounting 2-5

Setting the Output Flash Rate

DIP switch 10 sets the flash rate of the outputs (pilot lights). The
factory default setting is 1 Hz.

To change the flash rate, slide switch 10 to the appropriate ON/OFF
position.

DeviceNet Termination

Devices on end nodes of the DeviceNet network require termination.
If the RediSTATION is an end node, you must provide network
termination.

To terminate the RediSTATION, install a 121 ohm 1% metal film
resistor between the CAN_High and CAN_Low terminals on the
DeviceNet terminal block.

1

2

3

4

5

6

7

8

9

10

OFF = 0

ON = 1

Output Flash Rate

0 = 1 Hz (0.5 sec, On, 0.5 sec Off)
1 = 2 Hz (0.25 sec On, 0.25 sec Off)

DeviceNet Removable
Terminal Block

CAN_Low

CAN_High