Publication 2705-UM001A-EN-P

Overview of RediSTATION 1-7

Device Connection

The RediSTATION receives all power and communications through
the DeviceNet cable. A separate power supply is not required. This is
the only external connection to the RediSTATION.

The RediSTATION connects to the DeviceNet network using either the
sealed connector on the top of the unit or the DeviceNet terminal
block inside the enclosure.

DeviceNet Sealed Connector

On standard units, the DeviceNet cable attaches directly to the
DeviceNet connector at the top of the enclosure. The connector is
wired to the DeviceNet terminal block on the circuit board.

DeviceNet Terminal Block

On stations without a sealed connector, DeviceNet cable wires (2
communication, 2 power, 1 shield) connect to the terminal block
through the conduit at the top of the unit.

DeviceNet Connector

Pin #

Signal

Function

Color

1

SHIELD

Shield

Green

2

VDC+

Power Supply

Red

3

COM

Common

Black

4

CAN_H

Signal High

White

5

CAN_L

Signal Low

Blue

DeviceNet

Terminal Block

Pin #

Signal

Function

Color

1

COM

Common

Black

2

CAN_L

Signal Low

Blue

3

SHIELD

Shield

Uninsulated

4

CAN_H

Signal High

White

5

VDC+

Power Supply

Red

6

E. GND

Chassis Ground

Green

DeviceNet Connector

3

3

2

1

4

5

Conduit for DeviceNet Cable

1

6