Device connection, Devicenet sealed connector, Devicenet terminal block – Rockwell Automation 2705 RediSTATION Operator Interface User Manual User Manual
Page 13: Device connection -7
Publication 2705-UM001A-EN-P
Overview of RediSTATION 1-7
Device Connection
The RediSTATION receives all power and communications through
the DeviceNet cable. A separate power supply is not required. This is
the only external connection to the RediSTATION.
The RediSTATION connects to the DeviceNet network using either the
sealed connector on the top of the unit or the DeviceNet terminal
block inside the enclosure.
DeviceNet Sealed Connector
On standard units, the DeviceNet cable attaches directly to the
DeviceNet connector at the top of the enclosure. The connector is
wired to the DeviceNet terminal block on the circuit board.
DeviceNet Terminal Block
On stations without a sealed connector, DeviceNet cable wires (2
communication, 2 power, 1 shield) connect to the terminal block
through the conduit at the top of the unit.
DeviceNet Connector
Pin #
Signal
Function
Color
1
SHIELD
Shield
Green
2
VDC+
Power Supply
Red
3
COM
Common
Black
4
CAN_H
Signal High
White
5
CAN_L
Signal Low
Blue
DeviceNet
Terminal Block
Pin #
Signal
Function
Color
1
COM
Common
Black
2
CAN_L
Signal Low
Blue
3
SHIELD
Shield
Uninsulated
4
CAN_H
Signal High
White
5
VDC+
Power Supply
Red
6
E. GND
Chassis Ground
Green
DeviceNet Connector
3
3
2
1
4
5
Conduit for DeviceNet Cable
1
6