Operations 3-3

Error Mode

In error mode (LED turns red), the RediSTATION monitors the error
state for correct operation. Errors are critical or noncritical.

See the troubleshooting chart on page 4-2 for details on how to
recover from an error.

Resetting the Device

To reset the RediSTATION, you must cycle power to the unit or briefly
disconnect the DeviceNet connector.

Error Type

Description

LED State

Critical
(Not recoverable)

Failure of diagnostic tests during
powerup/reset mode

Solid Red

Over-temperature condition of
outputs during runtime

Changes to DIP switches during
runtime

Duplicate node address detected

Incorrect data rate

Non-critical
(Recoverable)

Pilot lamp burned out

Flashing Red

Pilot lamp wired incorrectly

I/O connection timeout