beautypg.com

Rockwell Automation 2705 RediSTATION Operator Interface User Manual User Manual

Page 41

background image

Publication 2705-UM001A-EN-P

Building a Custom RediSTATION 5-5

3. Mount the circuit board to the back of the 800T devices with the

DeviceNet terminal block oriented toward sealed connector/
conduit hole of enclosure. Use the two screws and plastic
spacers provided (2 sizes provided for different 800T device
depths). Tighten circuit board mounting screws to 14 in-lbs.

4. If you are not using a prewired DeviceNet connector, pull the

DeviceNet cable through the conduit at the top of the enclosure.
Then attach the 6 DeviceNet cable leads to the removable
terminal block connector.

Page 1-7 provides a description of the DeviceNet connections.

Spacers

Spacers

Circuit Board

Circuit Board

Mounting Screws

Toward sealed connector/
conduit hole of enclosure

ATTENTION

!

Do not connect the DeviceNet network to the
DeviceNet terminal block connector when power
is applied to the network or you may damage
the circuit board or the DeviceNet network.

ATTENTION

!

Use conduit fittings with proper seals on the
DeviceNet cable to maintain a watertight
enclosure.

Removable Terminal
Block Connector

Pin 1

Pin 6

Common

CAN Low

Shield

CAN High

VDC+

E GND