A-2 Specifications

Environment

Communications

Certifications

Ambient Temperature

Operating Temperature

0 to 55

°

C (32 to 131

°

F)

Storage

-40 to 85

°

C (-40 to 185

°

F)

Relative Humidity (non-condensing)

5 to 95%
50% max at 40

°

C (104

°

F)

Shock and Vibration

Shock (operating)

30G

Impulse Shock (non-operating)

50G

Vibration (operating)

2.5G at 58 to 2000 Hz
5 to 57 Hz 0.38mm displacement
(peak-to-peak)

Vibration (non-operating)

5.0G at 58 to 2000 Hz
5 to 57 Hz 0.76mm displacement
(peak-to-peak)

DeviceNet

Data Rates

125K, 250K, 500K BPS

Maximum Distance

500 meters (1600 feet) @125K
200 meters (600 feet) @250K
100 meters (300 feet) @500K

LED Indicator (Mod/Net Status)

Operating Status (Green/Red)

2705-T3DN1B42A (conduit entry)

UL Listed for Hazardous Location A196
Approved for Class I, Groups A, B, C, D,
Division 2, C-UL

2705-T3DN1A42A (sealed connector)

UL Listed A191, C-UL