4 resolving verify errors – Rockwell Automation AutoMax Enhanced Ladder Editor User Manual
Page 45

4Ć3
4.3
Specifying Whether To Include Warning
Messages When Verifying Programs
Select the Ignore Warnings option in the General tab options from
the Tools menu to prevent verify warnings from being displayed in
the Verify Output window and verify log file (if the log file is
generated). Verify error messages are always displayed in the
output window and log file. By default, the Editor includes verify
warning messages in the output window and log file of offline
programs that you verify. The Editor does not include warning
messages arising from committing online changes or placing the
program in Test Mode.
To prevent warning messages from displaying in the verify log
file
Step 1.
From the Tools menu, choose Options.
Step 2.
On the General tab, deselect the Ignore Warnings option
in the Verify group box.
Step 3.
To accept the change, click OK or Apply.
4.4
Resolving Verify Errors
The Verify Output window lists error messages and, if you choose,
warning messages that help you debug a program. Error messages
also include the rung number and grid location of the logic in which
the verify error occurred. For example,
This error:
In Rung #8 at location {4,1}
Variables of type Timer or Counter cannot be used on a coil.
Means:
The coil located in the fourth column of the first row in rung 8 has
a timer or counter associated with it.
Because the Verify Output window is separate from the program
window, you can easily switch between the program and the verify
messages as you troubleshoot your program.
Tip
To switch between the two windows, press CTRL+F6