Editing the message instruction – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 93

background image

Programming DH and DH+

Message Procedures

Chapter 6

6-2

The general steps for editing a DH or DH+ message procedure are:

1.

Create and edit the ladder program containing message instructions
that control execution of the message procedure.

2.

Allocate memory to the necessary data files.

3.

Create and edit the message procedure.

You can perform these steps through your programming terminal. Refer to
its user’s manual for detailed information on creating and editing the
ladder program.

You can also perform the third step through an RS-232-C data terminal
connected to an RS-232-C channel on a Peripheral Communication
Module (cat. no. 1775-GA).

Table 6.A gives an example of how to edit the message instruction in the
ladder program. For more details on ladder-program editing, refer to the
user’s manual for your programming device.

Table 6.A

Entering the Message Instruction into the Ladder Program

Prompt (if any)

Action

Start editing session.

Insert a new rung.

Enter the bit that conditions the message rung.

Enter the message instruction.

ENTER FILE
ADDRESS

Enter the address of the file where the message resides in

memory. This file should be binary.

ENTER SYSTEM
ADDRESS OR
SYMBOL

Enter the channel designation for the scanner:

F

or example, E2.3.4:

E2 is the module status

3 is the scanner module type

4 is the thumbwheel number

ENTER MESSAGE
TYPE

Enter the message type. This is always 1.

Enter a single assignment command or the name of a message

procedure. In this case, the message procedure name is PROC1.

End the editing session.

Editing the Message

Instruction