Diagnostics Methods
Chapter 7
7-14
Diagnostic Counters Reset Command
Use this command to reset to zero all the diagnostic counters in the remote
station.
Command block in data table:
0005 0006 0000 0007
Response block in data table:
0000 0004 4600 1900
Table 7.F
DH Diagnostic Counters
Byte:
This counter increments when the scanner:
1
receives an ACK with a bad CRC
2
does not receive an ACK before the timeout value
3
while master, detects a message transmission by another station
(contention)
4
receives an error in the received ACK
5
adds errors in bytes 1, 2, and 4
6
receives a WAK when no receive buffer space is available at the
remote station
7
does not detect a master on the link before its timeout period expires
and so assumes mastership
8
as master, does not receive a reply from its polling sequence that has
been narrowed done to a single station
9
receives an ACK even though it does not have mastership
10
receives an illegal packet of less than 6 bytes
11
receives a packet with an incorrect destination or a packet in which the
source is equal to the destination
12
(not used)
13
receives a packet with a bad CRC
14
received a frame that was beyond the legal limit of 250 bytes
15
does not have the buffer space for a received message
16
received a message that was previously received
17
received aborted frame (line noise)
18 & 19
successfully sent a message
20 & 21
successfully received a message
22 & 23
successfully sent a command
24 & 25
successfully receives a reply
26 & 27
successfully receives command
28 & 29
successfully sends a reply
30
can not send a reply