Diagnostics Methods

Chapter 7

7-16

Table 7.H

Data Sent in Response to a Diagnostic Status Command

Byte:

Bit:

Description:

1

Operating status of PLC-3 processor

0-1

00 = Program mode

01 = Test mode

10 = Run mode

2

Not used

3

0 = Normal

1 = Major processor fault

4

0 = Normal

1 = Shutdown request

5

0 = Normal

1 = Shutdown in effect

6Ć7

Not used

2

Type of station interface and processor

0Ć3

6 = scanner

4Ć7

4 = PLC-3 processor

3

all

Current context stored in bits 4 thru 7

4

all

Thumbwheel

5Ć6

all

Mode control word

The extended address of the mode control word is E0.0.0.8

7Ć8

all

Starting byte address of the diagnostic counters.

9

Series and revision number of the module.

Even though the scanners are series A, they appear as series E modules

0Ć3

0 = Revision A scanner

1 = Revision B scanner

etc.

4Ć7

0 = Series A 1 = Series B

etc.

10

Type of channel communications

0Ć1

0 = Inactive

1 = DH

2 = DH+

3 = other

2Ć3

0 = A/G or earlier S5 or SR5

1 = A/H or later S5

2 = A/H or later SR5

3 = unused

4Ć7

unused

11Ć14

all

The physical address of the unused word of PLC-3 system memory.

This is the physical address corresponding to the extended address

E60.0.0.0

15Ć18

all

The total number of words in the PLC-3 system memory

(both used and unused)