Binary command language appendix a – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual
Page 143
![background image](/manuals/579813/143/background.png)
Binary Command Language
Appendix A
A-15
Table A.E
Extended Addressing
Area
E#
.x
.x
.x
.x
.x
system status
E0
context = 0
section = 0
word = 0 Ć 20 not used
not used
module status
E2
module type =
1 - memory
2 - main processor
3 - scanner
5 - communication
adapter
6 - expansion
7 - S4B I/O scanner
8 - peripheral
communication
9 - DH II
interface
14 - memory
communication
thumbwheel switch =
1 Ć 15
module data
module data
module data
data table
E3
context = 1 Ć 15
section =
1 - output image
2 - input image
3 - timers
4 - counters
5 - integers
6 - floating point
7 - decimal
8 - binary
9 - ASCII
10 - high order int.
12 - pointers
13 - status
file =
0 Ć 999
0 Ć 999
0
0
0 Ć 999
0 Ć 999
0 Ć 999
0 Ć 999
0 Ć 999
0 Ć 999
0
0 Ć 999
structure =
0
0
0 Ć 9999
0 Ć 9999
0
0
0
0
0
0
0 Ć 9999
0
word =
0 Ć 07777 octal
0 Ć 07777 octal
0 Ć CTL, 1 Ć PRE, 2 Ć ACC
0 Ć CTL, 1 Ć PRE, 2 Ć ACC
0 Ć 9999
0 = lower 16 bits, 1 = upper 16 bits
0 Ć 9999
0 Ć 9999
0 Ć 9999
0 = lower 16 bits, 1 = upper 16 bits
0 = section/file, 1 = word
0 Ć 9999
ladder program E4
context = 1 Ć 15
section =
0 Ć program status
1 Ć main
2 Ć subroutine
3 Ć fault routine
rung =
0 Ć 32, 767
instruction =
0 Ć 32, 767
word =
0 Ć 32, 767
message
E5
context = 1 Ć 15
section =
1 Ć report generation
2 Ć rung comments
3 Ć terminal (MACROS)
4 Ć DH
5 Ć assistance (HELP)
message =
0 Ć 32, 767
word =
0 Ć 32, 767
not used
system
symbols
E6
context = 1 Ć 15
type = 1
symbol =
0 Ć 32, 767
word =
0 Ć 32, 767
not used
converted
procedures
E8
context = 1 Ć 15
section =
1 Ć report generation
message =
0 Ć 32, 767
word =
0 Ć 32, 767
not used
force table
E10 context = 1 Ć 15
force type =
0 Ć status
1 Ć forced output
2 Ć forced input
rack =
not used
0 Ć 64
0 Ć 64
word = 0
0 Ć 15
0 Ć 15
bit =
0 Ć input forces enabled/disabled
1 Ć output forces enabled/disabled
not used
not used