beautypg.com

Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual

Page 153

background image

Binary Command Language

Appendix A

A-25

Verify Block Command

Hex: 15

Parameters: Starting address, number of words, data to compare
with memory

Description: The processor can compare a block of data in memory to
reference data from an external device. The following command block
verifies the first three words in the binary section of the data table
(section eight):

STX

02

ISC

14

SIZ

0C

CMD

15

24

08

00

03

00

DAT

04

41

E1

02

E3

15

ETX

03

CHK

89

The data bytes store:

address mask (24 hex)
first address byte (08 hex)
second address byte (00 hex)
lower byte of size word (03 hex)
upper byte of size word (00 hex)
lower byte of the first data word (04 hex)
upper byte of the first data word (41 hex)
lower byte of the second data word (E1 hex)
upper byte of the second data word (02 hex)
lower byte of the third data word (E3 hex)
upper byte of the third data word (15 hex)

The processor responds to a verify block command with one of the
following response codes:

Response Codes

Hex

Description

00

Success

04

Address unknown

05

Address invalid - end of section

06

Access not allowed

08

Address not complete