Dh/dh+ error codes appendix b – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual
Page 169

DH/DH+ Error Codes
Appendix B
B-4
Error Code
Meaning
Associated
Commands
Error Type
84
reply
diagnostic status
Backplane error occurred during determination of the physical address of the end
of the ladder program or of the end of user memory. In polled mode, the
RSĆ232ĆC port has received a NAK, which causes a system reset.
reply
PLC/PLCĆ2 read,
write
Local PLCĆ3 backplane error (either memory parity or timeout/disconnect). In
polled mode, the RSĆ232ĆC port has received a NAK, which causes a system
shutdown.
reply
PLCĆ3 read and
write
Backplane error (memory parity or timeout/disconnect). In polled mode, the
RSĆ232ĆC port has received a NAK, which causes a system reset.
85
reply
diagnostic read
The command is an illegal request to read from the scanner's backplane window.
reply
PLC/PLCĆ2 read
•
PLCĆ3 file does not exist.
•
PLCĆ3 file is too small.
•
PLCĆ3 file is more than 65,535 words long.
reply
PLC/PLCĆ2 bit write
•
PLCĆ3 file does not exist.
•
Destination bits do not exist in PLCĆ3 file.
•
Length of PLCĆ3 file is greater than 65,535 words.
reply
PLC/PLCĆ2 word
write
•
Destination file does not exist in PLCĆ3 memory.
•
Destination word does not exist in the destination PLCĆ3 file.
•
Length of the destination file is greater than 65,535 words.
86
reply
PLC/PLCĆ2 bit write
Keyswitch setting at local PLCĆ3 controller prohibits access.
reply
PLC/PLCĆ2 word
write
Local keyswitch settings prohibit writing into desired destination file.
reply
PLCĆ3 write
Keyswitch setting disallows access to file.
87
reply
PLC/PLCĆ2/PLCĆ3
read and write
The local PLCĆ3 controller is in program mode. There may or may not be a major
system fault.
91
local
all
•
Handshaking lines on the RSĆ232ĆC link are not connected properly.
•
Multiple wacks on link.
92
local
all
The remote station specified does not acknowledge (ACK) the message.
94
local
all
Remote station is disabled.
112
local
all
Undefined operator in an assignment statement or expression.
114
local
all
Illegal expression syntax.
115
local
all
Illegal unary (prefix) operator in an expression.
117
local
all
Undefined data following a valid address in a CREATE command, or undefined
data following a valid symbol in a delete command.
121
local
all
Symbol undefined because it appears as the source in an assignment command
before it is defined. For example, a statement of the form A = A + 6 generates
this error if user symbol A has not appeared previously.
123
local
all
System symbol must be a symbolic address. This error occurs if a procedure
name is used in place of a symbolic address in an assignment statement or if the
system symbol referenced in an assignment does not exist.