Scanner hardware and installation chapter 1, Pass and fail indicators, Forces enabled indicator – Rockwell Automation 1775-S5_SR5,D17756.5.5 User Manual PLC-3 FAMILY I/0 User Manual
Page 13: I/o channel status indicators

Scanner Hardware and Installation
Chapter 1
1-4
Pass and Fail Indicators
The indicators labeled PASS and FAIL (Figure 1.2) keep you informed
about the general condition of the scanner:
PASS (green)
FAIL (red)
Meaning
on
off
normal operation
off
on
module fault
on
on
powerĆup or system reset
off
off
system is not on or module has lost power
Forces Enabled Indicator
The yellow indicator labeled FORCE (Figure 1.2) illuminates when I/O
forcing is enabled in the system.
I/O Channel Status Indicators
The four green indicators labeled CH1, CH2, CH3, and CH4 (Figure 1.2)
correspond to one of the four I/O channels.
Indicator
Status
Description
CHx
ON
Communication between scanner module and the I/O chassis
on the corresponding I/O channel is properly established.
Configured for
I/O scanning
FLASHING There is a fault on one or more of the I/O chassis on the
corresponding I/O channel.
OFF
No I/O chassis are configured on the corresponding I/O
channel or the channel is inactive.
CHx
ON
The channel is functioning properly.
Configured for
peerĆtoĆpeer
communication
FLASHING The input file is too small at the processor receiving data. The
slave or master does not exist. Communication retry.
OFF
The channel is inactive.
CHx
ON
The channel is functioning properly.
Configured for
backup
communication
FLASHING The input file is too small at the processor receiving data. The
partner is not responding.
OFF
The channel is inactive.