DH/DH+ Error Codes
Apendix B
B-5
Error Code
Meaning
Associated
Commands
Error Type
124
local
all
Illegal destination in an assignment command or invalid data following a number
on a command line. For example, the lines 5 = 4 + 1 or 6ASDFGHJ generate
this error code. The line $rbWERTYUI generates error code 140 (unrecognized
command).
125
local
all
Illegal modifier for the CREATE command. Accepted modifiers for the create
command are LOCAL and GLOBAL.
126
local
all
The CREATE command was specified, but the symbol did not begin with an @.
127
local
all
$ missing in a CREATE system symbol address command line.
129
local
all
Attempt to delete nonexistent symbol.
140
local
all
•
Unrecognized or ambiguous command.
•
Channel 4 not configured for DH/DH+.
142
local
all
Illegal data following GOTO command.
143
local
all
Illegal use of label (e.g., not in a procedure).
144
local
all
Label not found.
145
local
all
Duplicate label. User symbols must be distinct from labels.
146
local
all
Too many nested procedures.
147
local
all
Insufficient privilege for the specified operation. This error can occur when an
attempt is made, via the assignment command, to write into a major section of
memory in which the scanner does not have access privileges (namely, major
section 0, 1, or 2).
148
local
all
Unbalanced parenthesis in expression.
149
local
all
A procedure name is used in a field that requires a symbolic address or a user
symbol variable.
150
local
all
A label is used in a field that requires a symbolic address or a user symbol
variable.
154
local
all
Error in reading address for symbol entry.
156
local
all
Illegal symbol in expression.
159
local
all
Bad level specified in extended address:
•
More than nine levels specified in an extended address.
•
Something other than a ( or a number followed a in an extended address.
160
local
all
Unrecognized section specifier. An illegal character followed the $ in an address.
161
local
all
Bad timer or counter specification:
•
The first letter of the data table address is a T, C, or P, but four characters are
not in specification. Addresses that are incorrect causing this error include
$TAC:15, $C5:3, $TACCUM:23, etc.
•
The key data table word specifier is four characters long and began with a T,
C, or P, but it does match the legal word specifiers (e.g., $TACM:3).
•
No colon following a legal word specifier.