Output specifications – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual
Page 78

70
Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Appendix A Specifications
Output Specifications
The 1732E-OF4M12R module has the following input specifications.
Input range
Current input
Voltage input
32 mA, 275 mW
±30V, 20 mA, 25 mW
Input impedance
125 k
Ω
per channel
Accuracy
0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature, max
40 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration
Factory calibrated. Calibration is also supported through
RSLogix 5000.
Overload support
Current input
Voltage input
32 mA
30V continuous
Input Specifications – 1732E-IF4M12R
Attributes
Value
Output Specifications – 1732E-OF4M12R
Attributes
Value
Number of outputs
4
Resolution, min
16 bits
Data format
16-bit sign magnitude
Conversion rate
< 2 ms
Output type
Configurable as voltage or current per channel
Output range
Current output
Voltage output
0…20 mA, 4…20 mA
+/-10V, 10 mW
Short circuit protection, max
Current output
Voltage output
20 mA (0…20 mA mode)
20 mA per channel
Accuracy
0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature, max
40 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration
Factory calibrated. Calibration is also supported through
RSLogix 5000.