Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

51

Configurable Features for the Analog Input and Output Modules Chapter 4

64…65

Channel 3 Fault Value

66…67

Channel 3 Idle Value

68…69

Channel 3 Low Engineering

70…71

Channel 3 High Engineering

72…73

Channel 3 Low Clamp

74…75

Channel 3 High Clamp

76

Channel 3 Output Range

77

Channel 3 Fault State

78

Channel 3 Idle State

79

Channel 3 Enable Alarm Latch

80

Channel 3 Disable Alarms

81

Reserved (Ignore)

1732E-OF4M12R – Consumed Assembly Instance 106 Data Structure

Consumed
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0…1

Channel 0 Data

2…3

Channel 1 Data

4…5

Channel 2 Data

6…7

Channel 3 Data

1732E-IF4M12R – Produced Assembly Instance 105 Data Structure

Produced
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0…3

Reserved (must be zero)

4…5

Channel 0 Data

6…7

Channel 1 Data

8…9

Channel 2 Data

10…11

Channel 3 Data

12

Channel 0 Status

(1)

(1) This parameter is in Byte and has the following structure:

Bit 0 = Fault; Bit 1 = Calibration; Bit 2 = Low Alarm; Bit 3 = High Alarm; Bit 4 = Low Low Alarm; Bit 5 = High High
Alarm; Bit 6 = Underrange; Bit 7 = Overrange

13

Channel 1 Status

(1)

14

Channel 2 Status

(1)

15

Channel 3 Status

(1)

1732E-OF4M12R – Configuration Assembly Instance 101 Data Structure

Configuration
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0