Limits Configuration Tab
The Limits Configuration tab on the Module Properties dialog box lets you
program high and low limits, and disable and latch alarms per channel.
High Engineering
High engineering value helps determine the engineering units the signal
values scale into. The high engineering term corresponds to the high signal
value. The scaling equation used is shown below.
Low Engineering
Low engineering helps determine the engineering units the signal values
scale into. The low engineering term corresponds to the low signal value.
The scaling equation used is as follows:
Configuration tab
Field
Description
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Click Channel button to set limits
and alarm configuration for each
of the 4 channels.
Use the sliders to set limits. HI
sets High limits; and LO for Low.