Calibration tab, Port configuration tab – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual
Page 48
![background image](/manuals/579564/48/background.png)
40
Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Chapter 3 Configure Your Analog Input and Output Modules with RSLogix 5000 Software
Port Configuration Tab
To configure the Ethernet ports, click the Port Configuration tab.
This tab is only available for editing when the device is online.
To configure the ports:
Calibration Tab
The Calibration tab on the Module Properties dialog box lets you recalibrate the
module, if necessary. Calibration corrects any hardware inaccuracies on a
To
Then
Use the default port speed and duplex settings
Leave Auto-negotiate port speed and duplex
checked. This setting determines the actual speed
and duplex setting.
Manually configure your port’s speed and
duplex settings
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex
checkbox.
2. From the Current Port Speed pull-down menu,
choose a port speed.
3. From the Current Duplex pull-down menu,
choose the appropriate Duplex value, that is,
Half Duplex or Full Duplex.
IMPORTANT
Consider the following when you configure the module’s port settings:
• If the module is connected to an unmanaged switch, leave Auto-negotiate port
speed and duplex checked or the module will fail.
• If you are forcing the port speed and duplex with a managed switch, the
corresponding port of the managed switch must be forced to the same settings
or the module will fail.