Alarm configuration tab, To lear – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual
Page 34

26
Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Chapter 3 Configure Your Analog Input and Output Modules with RSLogix 5000 Software
2.
Do one of the following:
• Click Apply to store a change but stay on the dialog box to choose
another tab.
• Click OK if you are finished making changes.
Alarm Configuration Tab
The Alarm Configuration tab on the Module Properties dialog box lets you
program high and low limits, and disable and latch alarms per channel.
High Engineering
High engineering value helps determine the engineering units the signal
values scale into. The high engineering term corresponds to the high signal
value. The scaling equation used is shown below.
Low Engineering
One of four points used in scaling. The low engineering helps determine the
engineering units the signal values scale into. The low engineering term
corresponds to the low signal value. The scaling equation used is as follows:
Real Time Sample
(RTS)
This parameter instructs the module how often to scan its input channels
and obtain all available data. This feature is applied on a module-wide
basis.
Configuration tab
Field
Description
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering