Voltage meter calibrations – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual
Page 69
Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
61
Calibrate Your Modules Chapter 5
• For failed calibration, go to step
.
• For successful calibration, go to step
.
13.
If the calibration failed, click Retry to recalibrate the same channel.
This takes you back to steps
until you get successful calibration on
the channel.
14.
If the calibration is successful, click Next to start calibration on the next
channel (in this example, channel 1).
This takes you back to steps
. You will have to go through the same
steps for each of the next channels lined up for calibration.
15.
After successful calibration on the channel(s), click Finish to close the
Calibration Wizard.
Voltage Meter Calibrations
RSLogix 5000 software commands the module to output specific levels of
voltage. You must measure the actual level and record the results. This
measurement allows the module to account for any inaccuracies.
While you are online, you must access the Module Properties dialog box. See
Your 1732E-OF4M12R Configuration on page 30
Follow these steps to calibrate your module.
1.
Connect your voltage meter to the module.
2.
Go to the Configuration tab on the Module Properties dialog box.