Calibrate the output module (1732e-of4m12r), Current meter calibrations – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual
Page 66
58
Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Chapter 5 Calibrate Your Modules
Calibrate the Output
Module (1732E-OF4M12R)
Output calibration is a multi-step process that involves measuring a signal from
the module. This section has two parts, as shown in the table.
Current Meter Calibrations
RSLogix 5000 software commands the module to output specific levels of
current. You must measure the actual level and record the results. This
measurement allows the module to account for any inaccuracies.
While you are online, you must access the Module Properties dialog box. See
Your 1732E-OF4M12R Configuration on page 30
Follow these steps to calibrate your module.
1.
Connect your current meter to the module.
2.
Go to the Configuration tab on the Module Properties dialog box.
3.
At the Output Range, choose the range from the pull-down menu to
calibrate the channels. Click Apply.
Topic
Page
Current Meter Calibration
Voltage Meter Calibration