Develop Safety Applications

Chapter 6

7. Paste the producer controller’s SNN into the SNN field and click OK.

The safety network numbers match.

Produce a Safety Tag

Follow this procedure to produce a safety tag.

1. In the producing controllers project, create a user-defined data type

defining the structure of the data to be produced.

Make sure that the first data member is of the
CONNECTION_STATUS data type.

2. Right-click Controller Tags and choose New Tag.

3. Set the type as Produced, the class as Safety, and the Data Type to the user-

defined type you created in step

1

.

4. Click Connection and enter the number of consumers.

Module Properties Dialog Box in Consumer Project

Producer Controller Properties Dialog Box in Producer Project

Copy this SNN.

Paste the SNN here.