Adding cip safety i/o modules, Chapter 5, Configure, monitor, and replace cip safety i/o – Rockwell Automation 1756-L7x GuardLogix 5570 Controllers User Manual
Page 59: Add, configure, monitor, And replace cip safety i/o, Chapter

Rockwell Automation Publication 1756-UM022A-EN-P - November 2012
59
Chapter
5
Add, Configure, Monitor, and Replace
CIP Safety I/O
For more information on installation, configuration, and operation of CIP
Safety I/O modules, refer to these resources:
• Guard I/O DeviceNet Safety Modules User Manual, publication
• Guard I/O EtherNet/IP Safety Modules User Manual, publication
• POINT Guard I/O Safety Modules Installation and User Manual,
publicatio
• Logix Designer application online help
Adding CIP Safety I/O
Modules
When you add a module to the system, you must define a configuration for the
module, including the following:
• Node address for DeviceNet networks
You cannot set the node address of an CIP Safety I/O module on
DeviceNet networks via the Logix Designer application. Module node
addresses are set via rotary switches on the modules.
Topic
Page
Configure CIP Safety I/O Modules
Setting the Safety Network Number (SNN)
Using Unicast Connections on EtherNet/IP Networks
Setting the Connection Reaction Time Limit
Understanding the Configuration Signature
Reset Safety I/O Module Ownership
Monitor Safety I/O Module Status
Resetting a Module to Out-of-box Condition
Replacing a Module by Using the Logix Designer Application
Replacing a POINT Guard I/O Module by Using RSNetWorx for DeviceNet Software