System Overview

Selecting System Hardware

The GuardLogix system supports SIL 3 and PLe safety applications. The
GuardLogix controller is made up of a primary controller and a safety partner
that function together in a 1oo2 architecture.

Table 4

lists catalog numbers for

primary controllers and safety partners.

The safety partner must be installed in the slot immediately to the right of the
primary controller. The firmware major and minor revisions of the primary
controller and safety partner must match exactly to establish the control
partnership required for safety applications.

Primary Controller

The primary controller is the processor that performs standard and safety
functions and communicates with the safety partner for safety-related functions
in the GuardLogix control system. Standard functions include the following:

I/O control
Logic
Timing
Counting
Report generation
Communication
Arithmetic computations
Data file manipulation

The primary controller consists of a central processor, I/O interface, and
memory.

A three-position keyswitch on the front of the primary controller governs the
controller operational modes. The following modes are available:

RUN
PROGram
REMote - this software-enabled mode can be Program, Run, or Test

Table 4 - Primary Controller and Corresponding Safety Partner Catalog Numbers

Primary Controller

Safety Partner

1756-L71S, 1756-L72S, 1756-L73S

1756-L7SP

1756-L73SXT

1756-L7SPXT

Table 5 - Memory Capacity

Cat. No.

User Memory (RAM capacity)

Standard Tasks and Components

Safety Task and Components

1756-L71S

2MB

1 MB

1756-L72S

4 MB

2 MB

1756-L73S,1756-L73SXT

8 MB

4 MB