Viewing faults, Fault codes, Viewing faults fault codes – Rockwell Automation 1756-L7x GuardLogix 5570 Controllers User Manual
Page 120

120
Rockwell Automation Publication 1756-UM022A-EN-P - November 2012
Chapter 9
Monitor Status and Handle Faults
Viewing Faults
The Recent Faults dialog box on the Major Faults tab of the Controller
Properties dialog box contains two sub-tabs, one for standard faults and one for
safety faults.
The status display on the controller also shows fault codes with a brief status
message, as described beginning on page
Fault Codes
shows the fault codes specific to GuardLogix controllers. The type and
code correspond to the type and code displayed on the Major Faults tab of the
Controller Properties dialog box and in the PROGRAM object,
MAJORFAULTRECORD (or MINORFAULTRECORD) attribute.
The Logix5000 Controllers Major and Minor Faults Programming Manual,
publicatio
Logix controllers.
Table 40 - Major Safety Faults (Type 14)
Code
Cause
Status
Corrective Action
01
Task watchdog expired. User task has not completed in a
specified period of time. A program error caused an infinite
loop, the program is too complex to execute as quickly as
specified, a higher priority task is keeping this task from
finishing, or the safety partner has been removed.
Nonrecoverable
Clear the fault.
If a safety task signature exists, safety memory is re-initialized and the safety task
begins executing.
If a safety task signature does not exist, you must re-download the program to
allow the safety task to run.
Reinsert the safety partner, if it was removed.
02
An error exists in a routine of the safety task.
Recoverable
Correct the error in the user-program logic.
03
Safety partner is missing.
Nonrecoverable
Install a compatible safety partner.
04
Safety partner is unavailable.
Nonrecoverable
Install a compatible safety partner.
05
Safety partner hardware is incompatible.
Nonrecoverable
Install a compatible safety partner.
06
Safety partner firmware is incompatible.
Nonrecoverable
Update the safety partner so that the firmware major and minor revision matches
the primary controller.
07
Safety task is inoperable.
This fault occurs when the safety logic is invalid, for example
a mismatch in logic exists between the primary controller and
safety partner, a watchdog timeout occurred, or memory is
corrupt.
Nonrecoverable
Clear the fault.
If a safety task signature exists, safety memory is re-initialized via the safety task
signature and the safety task begins executing.
If a safety task signature does not exist, you must download the program again to
allow the safety task to run.
08
Coordinated system time (CST) not found.
Nonrecoverable
Clear the fault. Configure a device to be the CST master.
09
Safety partner nonrecoverable controller fault.
Nonrecoverable
Clear the fault and download the program. If the problem persists, replace the
safety partner.