Communicate over Networks

The Safety Network

The CIP Safety protocol is an end-node to end-node safety protocol that allows
routing of CIP Safety messages to and from CIP Safety devices through bridges,
switches, and routers.

To maintain high integrity when routing through standard bridges, switches, or
routers, each end node within a routable CIP Safety Control System must have a
unique reference. This unique reference is a combination of a safety network
number (SNN) and the node address of the network device.

Managing the Safety Network Number (SNN)

The SNN assigned to safety devices on a network segment must be unique. You
must be sure that a unique SNN is assigned to the following:

Each CIP Safety network that contains safety devices
Each chassis that contains one or more GuardLogix controllers

The SNN can be software-assigned (time-based) or user-assigned (manual).
These two formats of the SNN are described in the following sections.

Topic

Page

The Safety Network

43

EtherNet/IP Communication

49

ControlNet Communication

53

DeviceNet Communication

55

Serial Communication

57

TIP

Multiple safety network numbers can be assigned to a CIP Safety subnet or
a ControlBus chassis that contains more than one safety device. However,
for simplicity, we recommend that each CIP Safety subnet have
one, and only one, unique SNN.