Chapter
1
System Overview
Safety Application
Requirements
The GuardLogix 5570 controller system is certified for use in safety applications
up to and including Safety Integrity Level (SIL) 3 and Performance Level (e) in
which the de-energized state is the safe state. Safety application requirements
include evaluating probability of failure rates (PFD and PFH), system
reaction-time settings, and functional-verification tests that fulfill SIL 3/PLe
criteria.
GuardLogix-based SIL 3/PLe safety applications require the use of at least one
safety network number (SNN) and a safety task signature. Both affect controller
and I/O configuration and network communication.
For SIL 3 and PLe safety system requirements, including functional validation
test intervals, system reaction time, and PFD/PFH calculations, refer to the
GuardLogix 5570 Controller Systems Safety Reference Manual, publication
. You must read, understand, and fulfill these requirements prior to
operating a GuardLogix SIL 3, PLe safety system.
Safety Network Number
The safety network number (SNN) must be a unique number that identifies
safety subnets. Each safety subnet that the controller uses for safety
communication must have a unique SNN. Each CIP Safety device must also be
configured with the safety subnet’s SNN. The SNN can be assigned
automatically or manually.
For information on assigning the SNN, see
.
Topic
Page
Safety Application Requirements
Distinguishing between Standard and Safety Components
Controller Data Flow Capabilities