Install the controller into the chassis – Rockwell Automation 1756-L7x GuardLogix 5570 Controllers User Manual
Page 23
Rockwell Automation Publication 1756-UM022A-EN-P - November 2012
23
Install the Controller
Chapter 2
2. Install a ControlLogix power supply according to the corresponding
installation instructions.
Extreme environment (XT) controllers require an XT power supply.
Install the Controller into the
Chassis
You can install or remove a controller while chassis power is on and the system is
operating.
1. Insert the key into the primary controller.
2. Turn the key to the PROG position.
The safety partner does not have a keyswitch.
Cat. No.
Description
Series
Refer to These Installation
Instructions
1756-PA72
Power supply, AC
C
1756-PB72
Power supply, DC
1756-PA75
Power supply, AC
B
1756-PB75
Power supply, DC
1756-PAXT
XT power supply, AC
B
1756-PBXT
XT power supply, DC
WARNING: When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding. Repeated electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn contact may create
electrical resistance that can affect module operation.
IMPORTANT
The ESM begins charging when one of these actions occurs:
• The controller and ESM are installed into a powered chassis.
• Power is applied to the chassis that contains a controller with the ESM
installed.
• An ESM is installed into a powered controller.
After power is applied, the ESM charges for up to two minutes as indicated by
CHRG or ESM Charging on the status display.
1
2