Appendix B CompactLogix Backup on the DeviceNet Network

Node Address and Status Display

The seven-segment numeric display shows the following information about
the primary and secondary scanner modules in either Run or Idle modes.

TIP

If error codes other than those shown in these tables appear in the
display, refer to

Chapter 8

,

Troubleshooting

, for more information on

error codes.

Primary Scanner Module With Valid Backup Scanner Module

Run Mode

Primary

Secondary

Node Number

00

01 or 00

Status

00 (Run mode)

67 (Backup mode enabled) or 00 (Run mode)

Primary or Secondary

P - (Primary)

S - (Secondary)

Idle Mode

Primary

Secondary

Node Number

00

01 or 00

Status

80 (Idle mode)

67 (Backup mode enabled) or 80 (Idle mode)

Primary or Secondary

P - (Primary)

S - (Secondary)

Primary Scanner Module Without Valid Backup Scanner Module

Run Mode

Primary

Secondary

Node Number

00 or 01

01 or 00

Status

68 (No backup scanner present) or
00 (Run mode)

Undefined error or
69 (Backup scanner invalid CRC)

Primary or Secondary

P - (Primary)

--

Idle Mode

Primary

Secondary

Node Number

00 or 01

01 or 00

Status

68 (No backup scanner present) or
80 (Idle mode)

Undefined error or
69 (Backup scanner invalid CRC)

Primary or Backup

P - (Primary)

--