CompactLogix Backup on the DeviceNet Network Appendix B

This table describes the possible values this message may return when reading
the backup state of the DeviceNet scanner.

If the message reads
this value

The backup state of the DeviceNet scanner module is

0

Disabled

1

Primary scanner

2

Backup scanner

3

Invalid primary node address (for example, the node address
cannot be 62 or 63)

4

Faulted backup scanner module - CRC failure (for example,
the scanlists in the scanners do not match)

5

Faulted backup scanner module - backup node number
failure (for example, the backup scanner module is not using
a node number = the primary node number + 1)

6

Backup scanner module pending primary detection

254

Attempting primary access

67

Scanner in Backup Scanner mode

68

No backup scanner module present

69

Invalid backup scanner module CRC

255

Attempting backup access