Connect the inputs, Connect the inputs -14, Recommended surge suppressors – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual
Page 38

Publication 1760-UM001D-EN-P - September 2005
2-14 Installation
Recommended Surge Suppressors
Use the Allen-Bradley surge suppressors shown in the following table
for use with relays, contactors, and starters.
Connect the Inputs
Pico inputs switch electronically. Once you have connected a device
via an input terminal, you can reuse it as a relay contact in your
program as often as you like.
Connect devices such as buttons or switches to Pico input terminals.
Suppressor Device
Coil Voltage
Catalog Number
Bulletin 509 Motor Starter
Bulletin 509 Motor Starter
120V ac
240V ac
599-K04
599-KA04
Bulletin 100 Contactor
Bulletin 100 Contactor
120V ac
240V ac
199-FSMA1
199-FSMA2
Bulletin 709 Motor Starter
120V ac
1401-N10
Bulletin 700 Type R, RM Relays
ac coil
None Required
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
12V dc
12V dc
700-N22
700-N28
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
24V dc
24V dc
700-N10
700-N13
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
48V dc
48V dc
700-N16
700-N17
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
115-125V dc
115-125V dc
700-N11
700-N14
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
230-250V dc
230-250V dc
700-N12
700-N15
Bulletin 700 Type N, P, or PK Relay
150V max, ac or DC
700-N24
Miscellaneous electromagnetic
devices limited to 35 sealed VA
150V max, ac or DC
700-N24
+24 V
S1
com
I1
L1
L2
I1
I1