Troubleshoot Your Controller
You may sometimes find that Pico does not do exactly what you
expect. If this happens, read through the following notes which are
intended to help you solve some of the problems you may encounter.
Use the power flow display in Pico to check the logic operations in
the Pico circuit diagrams with reference to the switching states of
contacts and relays.
Only qualified persons should test Pico voltages while the device is in
operation.
Messages from the Pico
System
Pico System Messages on
the LCD
Explanation
Remedy
No display
Power interrupted
Turn on the power.
Pico LCD faulty
Replace the Pico.
Continuous display
TEST: AC
Self-test aborted
Replace the Pico.
TEST: EEPROM
TEST: DISPLAY
TEST: CLOCK
ERROR: I2C
Memory module removed or not
inserted correctly before saving
Insert the memory
module.
Memory module faulty
Replace the memory
module.
Pico is faulty
Replace the Pico.
ERROR: EEPROM
The memory for storing the
retentive values or the Pico circuit
diagram memory is faulty.
Replace the Pico.
ERROR: CLOCK
Clock error
Replace the Pico.
ERROR: LCD
LCD is faulty
Replace the Pico.
ERROR: ACLOW
Incorrect ac voltage
Test the voltage.
Pico is faulty
Replace the Pico.