7-6 Retention

Impulse Relay

Task:
After a power failure, the lights in a stairwell should resume their
previous state.

Contacts and relays used:

Signal diagram:

U = Supply voltage

Range A: Q1 was on prior to losing power. When power is re-applied
and the T2 timer expires, Q1 turns back on.

Range B: Q1 was on prior to losing power. When power is re-applied,
switch I1 is on, so Q1 stays off. Use time T2 to avoid brief flicker.

Range C: M15 is switched on and remains set until the next time I1 is
activated.

Coil

Function

T2

Enable after first cycle

I1

Push-button

Q1

Lamp output

M15

Impulse relay (retentive)

-----------TT2

I1--------

M15

M15-T2-----{Q1

00.10

TRG

RES

X

S

{

T2

+

Circuit Diagram:

Parameter Display:

U

I1

M15

Q1

T2

t

t

t

A

B

C