Parameters in the 1203-GK5 Module and 1336-GM5 Board
Parameters
The following table provides information on the parameters in the
1203-GK5 module and 1336-GM5 board.
Important:
When accessing this parameter set
through the
DeviceNet Parameter Class, add
the adapter parameter number to
the number of the last parameter of the SCANport device.
When
accessing this parameter set
through the vendor-specific SCANport
Variables-Linear Class, add the adapter parameter number to 0x4000.
.
1 DN-SW1 Setup
Displays the switches settings onSW1.
Important: The present settings may not be the condition under which
the module is operating. They will be the values that are read after a
SCANport/DeviceNet power cycle.
Refer to Chapter 2, Configuring the 1203-GK5 Module or 1336-GM5
Board, for more information.
Parameter Number
1
Parameter Type
Read Only
Factory Default
0000 0000
Power Cycle Required
No
Datalink A Enabled
Datalink B Enabled
Datalink C Enabled
Datalink D Enabled
Not Used
Hold Last State/Zero Data
Disable Comm Loss Fault
Disable Pgm/Idle Fault
Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1
2 DN-SW2 Node Adx
Displays the node address as it is set on SW2, switches 1 through 6.
Important: This setting is not the setting used by the adapter if either
of the following conditions is true:
• The switches were reset and the adapter was not power cycled.
• Switches 7 and 8 on SW2 are both set to on, so the adapter reads
the node address from parameter 4.
Refer to Chapter 2, Configuring the 1203-GK5 Module or 1336-GM5
Board, for more information.
Parameter Number
2
Parameter Type
Read Only
Factory Default
63
Minimum Value
0
Maximum Value
63
Power Cycle Required
No
3 DN-SW2 Data Rate
Displays the Data Rate as it is set on SW2, switches 7 and 8.
Important: This setting is not the setting used by the adapter if either
of the following conditions is true:
• The switch was reset and the adapter was not power cycled.
• Switches 7 and 8 on SW2 are both set to on, so the adapter reads
the data rate from parameter 5.
Refer to Chapter 2, Configuring the 1203-GK5 Module or 1336-GM5
Board, for more information.
Parameter Number
3
Parameter Type
Read Only
Factory Default
125 kbps
Minimum Value
0
Maximum Value
3
Units
0 = 125
1 = 250
2 = 500
3 = Program using network
➀
Power Cycle Required
No
➀
When set to this position, the data rate and node address are programmed over
the DeviceNet network using DeviceNet Manager software.