beautypg.com

Rockwell Automation 1203-GK5 DeviceNet Communications Module FRN 1.xxx-3.xxx User Manual

Page 22

background image

2-2

Configuring the 1203-GK5 Module or 1336-GM5 Board

On the 1203-GM5 board, DIP switches are found in the following
location.

Figure 2.2
Switches on the 1336-GM5 Board

Configuring the 1203-GK5 Module
or 1336-GM5 Board

If you do not intend to use the factory-default settings, you must
configure the module using its DIP switches. Using the DIP switches,
you can configure the following features:

DeviceNet network data rate.

Node address for the adapter.

Datalinks.

Adapter reaction when the network fails.

Adapter reaction when the controller is idle (e.g., scanner or
controller is in program mode).

AB0938

SW1.1 = Datalink A
SW1.2 = Datalink B
SW1.3 = Datalink C
SW1.4 = Datalink D
SW1.5 = Not Used
SW1.6 = Zero Data / Hold Last State
SW1.7 = Fault on Comm Loss
SW1.8 = Fault On Pgm / Idle

SW2.1 – SW2.6 = Node Address Selection
SW2.7 – SW2.8 = Data Rate Selection

SW2

SW1

DeviceNet

Communications

Module

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

This manual is related to the following products: