ODVA Interface Parameter Descriptions
C-7
ODVA Drive Profile Interface
Parameters (Continued)
Parameter
Number
Parameter
Group
Name and Description
Object
Mapping
(Class-
Instance-
Attribute)
Min./Max.
Range
Units
Factory
Default
45
AC Drive
Extension
[Input Mode]
This read/write parameter configures the TB3 control inputs for either
3-wire or 2-wire run forward/run reverse control. It also enables/disables
network control of the run forward/run reverse control.
Important: Power must be cycled for the change to take effect.
0 = 3-wire control.
1 = 2-wire control.
2 = Network control.
3 = Momentary Run Forward/Run Reverse control.
0x2A-1-146 0 to 3
0
46
AC Drive
Extension
[Output Mode]
This read/write parameter configures the TB3 relay output functionality.
0 = Drive Ready/Faulted.
1 = At Frequency.
2 = Drive Running.
3 = Reverse.
4 = Motor Overload.
5 = Ramp Regulated.
6 = Above Frequency.
7 = Above Current.
8 = Above DC Bus Voltage.
9 = Retries Exhausted.
0x2A-1-147 0 to 9
Numeric
Value
0
47
AC Drive
Extension
[Output Threshold]
This read/write parameter determines the on/off point for the TB3 output
relay when P46 - [Output Mode] is set to 6, 7, or 8.
0x2A-1-148 0 to 815
Numeric
Value
0
48
AC Drive
Extension
[PWM Frequency]
This read/write parameter sets the carrier Frequency for the PWM output
waveform. The chart below provides derating guidelines based on the
PWM Frequency setting.
0x2A-1-149 2.0 to 8.0
0.1 kHz
4.0 kHz
49
AC Drive
Extension
[Restart Tries]
This read/write parameter sets the maximum number of times the drive
will attempt to reset a fault and restart the drive.
0x2A-1-150 0 to 9
Numeric
Value
0
50
AC Drive
Extension
[Restart Time]
This read/write parameter sets the time between restart attempts.
0x2A-1-151 0.5 to 300.0 0.1 Sec-
onds
10.0
Seconds
51
AC Drive
Extension
[DB Enable]
This read/write parameter enables/disables dynamic braking.
0 = Disable.
1 = Enable.
Important: This parameter can not be programmed while the drive is
running.
0x2A-1-152 0 to 1
Numeric
Value
0
!
ATTENTION: Changing this parameter value may
cause unpredictable network conditions, resulting in
equipment damage, personal injury, or death. Ensure
that you understand how changing this parameter
affects your application.