Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 77
Publication 0160-5.5 - September 1997
B-16
DeviceNet Information
Class Code 0xB3 —
160 Parameter Table Object
(Continued)
Common Services
Attribute ID
Access
Rule
Parameter Name
Data
Type
Units
Description
64
Get/Set
[Preset Frequency 3]
UINT
0.1 Hz
Sets command frequency when selected.
65
Get/Set
[Preset Frequency 4]
UINT
0.1 Hz
Sets command frequency when selected.
66
Get/Set
[Preset Frequency 5]
UINT
0.1 Hz
Sets command frequency when selected.
67
Get/Set
[Preset Frequency 6]
UINT
0.1 Hz
Sets command frequency when selected.
68
Get/Set
[Preset Frequency 7]
UINT
0.1 Hz
Sets command frequency when selected.
69
Get/Set
[Accel Time 2]
UINT
0.1 Seconds
Sets acceleration rate for presets 4 to 7.
70
Get/Set
[Decel Time 2]
UINT
0.1 Seconds
Sets deceleration rate for presets 4 to 7.
71
Get/Set
[IR Compensation]
USINT
1%
Adds a voltage to the output based on the torque current.
72
Get/Set
[Slip Compensation]
USINT
0.1 Hz
Compensates for the inherent slip of the motor.
73
Get/Set
[Reverse Disable]
BOOL
Numeric Value
Setting to 1 disables the reverse.
74
Get/Set
[Analog Select]
BOOL
Numeric Value
Selects between unipolar and bipolar analog input.
75
Get/Set
[Analog Input Minimum]
INT
0.1%
Sets the percent of the analog input used to represent
P32 - [Minimum Frequency].
76
Get/Set
[Analog Input Maximum]
INT
0.1%
Sets the percent of the analog input used to represent
P33 - [Maximum Frequency].
78
Get/Set
[Compensation]
BOOL
Numeric Value
Setting to 1 enables the compensation.
This parameter applies only to the Analog Signal Follower model.
This parameter applies only to the Preset Speed model.
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single