Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 96
Publication 0160-5.5 - September 1997
ODVA Interface Parameter Descriptions
C-5
ODVA Drive Profile Interface
Parameters (Continued)
Parameter
Number
Parameter
Group
Name and Description
Object
Mapping
(Class-
Instance-
Attribute)
Min./Max.
Range
Units
Factory
Default
29
AC Drive
[High Speed Limit]
This read/write parameter sets the highest speed in RPM that the drive
will output continuously.
0x2A-1-21
0 to 32000
1 RPM
1800 RPM
30
AC Drive
Extension
[Bus Voltage]
This read only parameter contains the DC Bus Voltage level.
0x2A-1-105 0 to 800
1 Volt
–
31
AC Drive
Extension
[Heatsink Temp]
This read only parameter contains the temperature of the drive heatsink.
0x2A-1-108 0 to 150
1
°
C
–
32
AC Drive
Extension
Drive Status
This read only parameter contains the drive status in binary coded for-
mat.
bit 0 - Running.
bit 1 - Forward.
bit 2 - Accelerating.
bit 3 - Decelerating.
bit 4 - Faulted.
bit 5 - Reverse latched.
bit 6 - At Frequency.
0x2A-1-109 000000 to
111111
Binary
Number
–
33
AC Drive
Extension
[Drive Type]
This read only parameter contains a coded drive rating used by Allen-
Bradley service personnel.
0x2A-1-110 Numeric
Value
Numeric
Value
–
34
AC Drive
Extension
[Control Version]
This read only parameter contains the version of the drive firmware.
Used by Allen-Bradley service personnel.
0x2A-1-111 Numeric
Value
Numeric
Value
Numeric
Value
35
AC Drive
Extension
[Input Status]
This read only parameter contains the open (0) closed (1) state of the
discrete inputs in binary coded format.
bit 0 - Preset 1.
bit 1 - Preset 2.
bit 2 - Preset 3.
bit 3 - Undefined.
bit 4 - Reverse.
bit 5 - Stop.
bit 6 - Start.
bit 7 - Undefined.
0x2A-1-112 000000 to
111111
Binary
Number
–
36
AC Drive
Extension
[Power Factor Angle]
This read only parameter contains the angle in electrical degrees
between motor voltage and motor current.
0x2A-1-113 0.00 to
90.00
degrees
0.01
degrees
–