Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 97
![background image](/manuals/577946/97/background.png)
Publication 0160-5.5 - September 1997
C-6
ODVA Interface Parameter Descriptions
ODVA Drive Profile Interface
Parameters (Continued)
Parameter
Number
Parameter
Group
Name and Description
Object
Mapping
(Class-
Instance-
Attribute)
Min./Max.
Range
Units
Factory
Default
37
AC Drive
Extension
[Stop Mode Select]
This read/write parameter determines the stopping mode used by the
drive when a stop is initiated.
0 = Ramp to stop.
1 = Coast to stop.
2 = DC Injection Braking.
0x2A-1-114 0 to 2
Numeric
Value
0
38
AC Drive
Extension
[Maximum Voltage]
This read/write parameter sets the highest voltage the drive will output.
Important: Must be greater than or equal to P2 - [Motor Rated Volt].
0x2A-1-137 20 to 460
1 Volt
460 or 230
39
AC Drive
Extension
[Boost Select]
This read/write parameter sets the boost voltage and redefines the Volts
per Hz curve.
0x2A-1-138 0 to 12
Numeric
Value
4
40
AC Drive
Extension
[Skip Frequency]
This read/write parameter works in conjunction with P41 - [Skip Fre-
quency Band] to create a range of frequencies at which the drive will not
operate continuously.
0x2A-1-139 0 to 240
1 Hz
240 Hz
41
AC Drive
Extension
[Skip Frequency Band]
This read/write parameter determines the band around
P40 - [Skip Frequency]. The actual band width will be 2 times Skip Band
RPM - 1/2 the band above and 1/2 the band below. A value of zero will
disable the skip frequency.
0x2A-1-140 0 to 30
1 Hz
0 RPM
42
AC Drive
Extension
[Overload Select]
This read/write parameter selects the derating factor for the I2T overload
function.
0x2A-1-141 0 to 2
Numeric
Value
0
43
AC Drive
Extension
[DC Hold Time]
This read/write parameter defines the time that P44 - [DC Hold Volts]
voltage will be applied to the motor when P37 - [Stop Mode Select] is
set to either DC Brake or Ramp to Stop mode.
0x2A-1-144 0 to 15
1 Second
0 Seconds
44
AC Drive
Extension
[DC Hold Volts]
This read/write parameter sets the DC Voltage level applied to the motor
during braking when P77 - [Stop Mode Select] is set to either DC Brake
or Ramp to Stop mode.
0x2A-1-145 0 to 115
1 Volt
0 Volt
!
ATTENTION: Changing this parameter value may
cause unpredictable network conditions, resulting in
equipment damage, personal injury, or death. Ensure
that you understand how changing this parameter
affects your application.