Class code 0xb3 — 160 parameter table object – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 75

Publication 0160-5.5 - September 1997
B-14
DeviceNet Information
Class Code 0xB3 —
160 Parameter Table Object
Instance 1 Attributes:
Class Attributes: None Supported
Number of Instances: 1
Attribute ID
Access
Rule
Parameter Name
Data
Type
Units
Description
This Bulletin 160 SSC specific object implements all of the parameters in the 160 SSC parameter table as instance attributes of the object. For example,
attribute #1 corresponds to P01 - [Output Frequency]. This give you the ability to configure a drive via DeviceNet using attribute numbers that are pub-
lished as parameter numbers in the Bulletin 160 SSC User Manual. Important: Attributes 9 and 12 shown below do not match what is published in the Bul-
letin 160 SSC User Manual.
01
Get
[Output Frequency]
UINT
0.1 Hz
Frequency at TB2 terminals T1, T2, T3.
02
Get
[Output Voltage]
UINT
1 Volt
Voltage at TB2 terminals T1, T2, T3.
03
Get
[Output Current]
UINT
0.01 Amperes
Current at TB2 terminals T1, T2, T3.
04
Get
[Output Power]
UINT
0.01 kW
Power at TB2 terminals T1, T2, T3.
05
Get
[Bus Voltage]
UINT
1 Volt
DC Bus voltage level.
06
Get
[Frequency Command]
UINT
0.1 Hz
Commanded frequency.
07
Get
[Last Fault]
USINT
Numeric Value
Coded last fault number.
08
Get
[Heatsink Temp]
USINT
1 C
Temperature of the drive heatsink.
09
Get
[Drive Status]
USINT
Binary Number
Status of drive in binary coded format.
10
Get
[Drive Type]
UINT
Numeric Value
Used by Allen-Bradley field service personnel.
11
Get
[Control version]
UINT
Numeric Value
version of drive firmware used.
12
Get
[Input Status]
USINT
Binary Number
Open (0) Closed (1) state of drive’s discrete inputs.
13
Get
[Power Factor Angle]
UINT
0.1
Angle (electrical degrees) between V and I.
14
Get
[Memory Probe]
UINT
Numeric Value
Used by Allen-Bradley service personnel.
16
Get
[Analog Input]
INT
0.1%
The analog input as a percent of full scale.
30
Get/Set
[Accel Time 1]
UINT
0.1 Seconds
Time to ramp from 0 Hz to maximum frequency.
31
Get/Set
[Decel Time 1]
UINT
0.1 Seconds
Time to ramp from maximum frequency to 0 Hz.
32
Get/Set
[Minimum Frequency]
USINT
1 Hz
Lowest continuous output frequency.
33
Get/Set
[Maximum Frequency]
USINT
1 Hz
Highest continuous output frequency.
34
Get/Set
[Stop Mode Select]
USINT
Numeric Value
Determines stop mode used.
35
Get/Set
[Base Frequency]
USINT
1 Hz
Set to motor’s nameplate frequency.
36
Get/Set
[Base Voltage]
UINT
1 Volt
Set to motor’s nameplate voltage.
37
Get/Set
[Max Voltage]
UINT
1 Volt
Highest voltage the drive will output.
38
Get/Set
[Boost Select]
USINT
Numeric Value
Sets the volts/Hz relationship.
!
ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Ensure that you
understand how changing this parameter
affects your application.