Instance data format, Output assemblies – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 80
Publication 0160-5.5 - September 1997
DeviceNet Information
B-19
Instance Data Format
Output Assemblies
➀
If speed references are outside of their min/max limits, the drive ignores them and previous speed reference will be maintained.
Instance 1 Data Format (Basic Contactor Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Run
Instance 2 Data Format (Basic Overload Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset
Instance 3 Data Format (Basic Motor Starter Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset
Run
Instance 4 Data Format (Extended Contactor Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
RunRev
RunFwd
Instance 5 Data Format (Extended Motor Starter Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset
RunRev
RunFwd
Instance 20 Data Format (Basic Speed Control Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset
RunFwd
1
2
➀
Speed Reference RPM (Low Byte)
3
➀
Speed Reference RPM (High Byte)
Instance 21 Data Format (Reversing Speed Control Output Assembly)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
NetRef
Net Control
Fault Reset
RunRev
RunFwd
1
2
➀
Speed Reference RPM (Low Byte)
3
➀
Speed Reference RPM (High Byte)
Instance 100 Data Format (Reversing Speed Control Output Assembly (Hz)
This output assembly type is only available for use when Parameter #15 (Interface Select) is set to “0=Bulletin 160 SSC Interface.”
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault Reset
RunRev
RunFwd
1
2
➀
Internal Frequency (0.1 Hz) (Low Byte)
3
➀
Internal Frequency (0.1 Hz) (High Byte)