Troubleshooting, Harmonicguard active filter fault, Interface module problem – TCI HGA Manual User Manual
Page 98
![background image](/manuals/573979/98/background.png)
98
Troubleshooting
HarmonicGuard Active Filter Fault
If the display indicates a fault has occurred proceed to the fault screen by choosing the “Fault” menu screen
button. To see if this is a recurring fault hit the “History” button from inside the “Fault” screen. To clear a
fault press the “Reset” button from inside the “Fault” Screen or the “Stop” button from any screen.
Warning
Only qualified electricians should carry out all electrical installation & maintenance work on the HGA.
Disconnect all sources of power to the drive and HGA before working on the equipment. Do not
attempt any work on a powered HGA.
This HGA unit contains high voltages and capacitors. Wait at least five minutes after disconnecting
power from the filter before attempting to service the conditioner. Check for zero voltage between all
terminals on the capacitors. Also, check for zero voltage between all phases of the input and output
lines. All maintenance and troubleshooting must be done by a qualified electrician. Failure to follow
standard safety procedures may result in death or serious injury. Unless an external disconnect
means has been provided everything ahead of the filter circuit breaker, including the reactors,
will still be energized.
Interface Module Problem
The Interface Module is comprised of four major components; the HMI display, the Interface PCB, the
cabling and an optional Gateway. The Interface PCB contains diagnostic LEDs. The locations of the LEDs
are shown in Figure 8.3, and their functions are listed in Table 8.1.
Figure 8.3 – Communications Board LED placement
Table 8.1 – LED Functions
LED
LED Color
Description (LED Color)
D1
Green
AUX 1
D3
Green
AUX 2
D4
Green
Running Relay Energized
D5
Green
Power-On Relay Energized
D6
Green
Fault Relay Energized
D7
Green
Current Limit Relay Energized
D12
Green
RS485 Communication is active from converter
D13
Orange
RS485 Communication is active to converter
D14
Green
Input Run Command Present