Line/Load Status Sub Screen
The Line/Load Status Sub Screen shows more specific information regarding the source and load voltage,
current, power, power factor and THD measurements.
Figure 7.6 – Line/Load Status Sub Screen
Table 7.6 – Line/Load Status Sub Screen Elements
Screen Element
Description
Volts Display
Displays the current utility phase to phase line voltage in Volts
RMS.
Current Display
Displays the current line/load phase current in Amps RMS.
NOTE: the displayed current is affected by the CT Ratio
configuration on the “Setup” page.
Power Display
The three phase real power (P) of the line/load in kW.
Apparent Power
The three phase apparent power (S) of the line/load in kVA.
Power Factor
Display
Displays current line/load power factor. 1.00 indicates unity power
factor. A negative power factor indicates lagging power factor.
I THD Display
Displays the Total Harmonic Distortion of the utility Line/Load
current as a percentage.
V THD Display
Displays the Total Harmonic Distortion of the utility line Voltage as
a percentage.
I THD Ref Display
Displays the reference Total Harmonic Distortion of the utility
Line/Load current in percent. This THD display is the uncorrected
THD of the Line/Load taken when the HarmonicGuard Active filter
was not running.
Run/Stop Button
Runs and stops the HarmonicGuard Active filter.
Back Button
Returns to the main Status Screen