Table 3.6 – HarmonicGuard Active filter Technical Specifications
*
P
*Please consult TCI regarding optimum filter performance when applied to DC drives.
Voltage ratings
480V, 3 phase, 60 Hz, three wire systems
Phase Sequence
Positive phase rotation: A-B-C (or L1-L2-L3)
Load types
3-phase diode bridge rectifier loads such as PWM AC drives
*3-phase controlled rectifier (SCR or thyristor) loads such as DC drives
Current ratings
See Ratings in Standard Product Rating and Dimensions tables.
Maximum elevation
1,000 meters (3,280 feet) For every 100 meters (328 feet) over 1,000,
de-rate by 1%. Maximum elevation is 2,000 meters (6,560 feet).
Maximum Ambient
operating temperature
All units 40°C (104°F) except 45 & 90 amp open chassis units rated for
50°C (122°F) surrounding air. Product must be equipped with special
cooling provisions for operation above this temperature.
Minimum Ambient
operating temperature
0°C (32°F) for open chassis and Type 1 enclosures.
-20°C (-4°F) for Type 3R enclosures.
Product must be equipped with special heating provisions for operation
below this temperature.
Ambient storage temperature
-20°C to 60°C for Open Chassis and UL Type 1
-40°C to 60°Cfor UL Type 3R
Maximum humidity,
operating or storage
95%, non-condensing
Enclosure options
Standard: Open Chassis and UL Type 1 enclosed, UL Type 3R enclosed
Contact TCI Technical Support for other enclosure options.
Agency approvals or
certifications
UL and cUL Listed
Electronic overload / over
current protection
Factory calibrated processor controlled electronic over current fault, and
over load.
Over current protection:
All units have internal circuit breaker for protection of the converter
section of the HGA. The customer must supply branch circuit
protection.
Status indication LEDs
Numerous LED indicators on converter unit