TCI HGA Manual User Manual
Page 83

83 
 
Figure 7.8 – VLine & ILine Waveform Plot of a Properly Connected
HarmonicGuard Active filter (unit in stopped state)
Note: The example VLine & ILine Waveform Plot screens apply to rectifier loads only. For low power factor 
loads the VLine & ILine waveform screen will appear different. 
Table 7.8 shows what the VLine & ILine Waveform Plot Sub Screen would look like with various 
connection errors present in the system. 
Table 7.8 – VLine & ILine Waveform Plot Screen Examples when
Typical Connections Errors Present in System
VLine & ILine Waveform Plot Sub Screen with 
Rectifier Load 
Connection 
Error 
Description 
Connection Error 
Resolution 
Phase rotation is 
Incorrect: 
Phase A leads 
Phase C instead 
of Phase C 
leading Phase A. 
To correct swap 
Phase A and Phase 
C HarmonicGuard 
Active filter power 
connections AND 
swap Phase A and 
Phase C system CT 
current feedback 
then recheck plot. 
