TCI HGA Manual User Manual
Page 7

7 
 
 
1) Verify unit external connections 
• Phase A, B, C power connection,
with positive A-B-C phase rotation expected
• CT H1 Terminal is pointing toward the source
• CT feedback on phases A & C to TB-1 
• Leave CT shorting bars in place on TB-1 
• With the HGA circuit breaker open, 
energize the source to the HGA
• Close the HGA circuit breaker
• Fans and HMI should come on in < 5 seconds 
• HMI will start on Home screen 
• Load(s) have an integral 5% line reactance or 
equivalent dc bus choke
Warning
Hazardous voltages are present when 
unit is energized 
 
NOTE: Language Selection 
• The active filter supports several languages
including English, French and Spanish
• Press “Setup” to navigate to Setup screen and
press the “Language Setup” button.
• Select language setting from the language setup
pop-up screen.
 
2) Converter check - 1 
• Press “Setup” to navigate to Setup screen
• Ensure that “Auto Start En,” “Harmonic
Correct En,” and “PWR Fact Correct En” 
buttons are off (blue color) 
• If they are ON (green) press them to toggle to OFF
(blue)
• Press “Save Settings”
• Press “Status” to navigate to Status screen 
• Press “Home” to navigate to Home screen 
 
NOTE: Built In Sensor Wiring Error Detection 
• The active filter has an automatic sensor wiring
error detection algorithm built in to the controls.
• If a sensor wiring error is detected please reference
the Sensor Error Auto Detection section on page 
93. 
!