Warnings and Cautions
Dangerous Voltage Warning: warns of
situations in which a high voltage can
cause injury and/or equipment damage.
The text next to this symbol describes
ways to avoid danger.
General Warning: warns of situations
that can cause physical injury and/
or equipment damage by means other
than electrical. The text next to this
symbol describes ways to avoid the
danger.
General Safety Instructions
Be sure to read, understand, and follow
all safety instructions.
Only qualified electricians should
carry out all electrical installation and
maintenance work on capacitor bank.
All wiring must be in accordance with
the National Electrical Code (NEC)
and/or any other codes that apply to
the installation site.
Disconnect all power before working
on the equipment. Do not attempt any
work on a powered capacitor bank.
The capacitor bank and other
connected equipment must be properly
grounded.
The terminals and connected cables
are at a dangerously high voltage when
power is applied.
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
!
!
!
!
Torques to be used when rating is not
marked explicitly on connection block
240V
8kvar
awg 8 - 2/0, 35.5 lb. - in.
12kvar
awg 8 - 2/0, 35.5 lb. - in.
25 - 30kvar
awg 8 - 2/0, 35.5 lb. - in.
all other kvars
awg 1 - 4 (35 lb. - in.) 6 - 14 (30lb. - in.)
400V
1 to 90kvar
awg 1 - 4 (35lb. - in.) 6 - 14 (30lb. - in.)
above 30kvar
awg 8 - 2/0, 35.5lb. - in.
480V
45 to 90kvar
awg 8 - 2/0, 35.5lb. - in.
105 to 150kvar
awg 3/0 - 350mcm, 230lb. - in.
above 150kvar
awg 4 - 300 mcm, 275lb. - in.
600V
60 to 105kvar
awg 8 - 2/0, 35.5lb. - in.
120 to 180kvar
awg 3/0 - 350mcm, 230lb. - in.
above 180kvar
awg 4 - 300mcm, 275lb. - in.