2 monitoring the dc-bus voltage, 3 monitoring the logic supply, 4 monitoring the heatsink temperature – Lenze 931E/K Small Drives Control User Manual
Page 122: Monitoring the dc−bus voltage, Monitoring the logic supply, Monitoring the heatsink temperature, Troubleshooting and fault elimination
Troubleshooting and fault elimination
Error monitorings in the 931E/K
Monitoring the DC−bus voltage
l
122
SW−HB 13.0002−EN 4.1
9.1.2
Monitoring the DC−bus voltage
ƒ
Overvoltage monitoring:
The overvoltage monitoring for the DC bus will respond if the DC−bus voltage exceeds
the operating voltage range. After this, the power stage will be switched off.
ƒ
Undervoltage monitoring: The undervoltage monitoring will respond if the DC−bus
voltage falls below the lower voltage threshold, see the chapter "DC−bus
monitoring". (
¶ 143)
The response to this error can be parameterised for applications that require "no−load
traversing" of the DC bus or machine set−up with a reduced DC−bus voltage.
9.1.3
Monitoring the logic supply
ƒ
24 V over/undervoltage monitoring:
The logic supply of the 931E/K servo positioning controller is monitored. When the
logic supply is too high or too low, an error message will be activated.
ƒ
Internal operating voltages:
All internal operating voltages such as the 3.3 V supply for the processor are monitored.
9.1.4
Monitoring the heatsink temperature
ƒ
Temperature derating:
With high temperatures, the permissible maximum current will be derated to ensure
a long service life of the 931E/K servo positioning controller.
ƒ
Switch−off in the event of overtemperature:
A linear temperature sensor is used to measure the heatsink temperature of the power
stage. When the temperature limit is reached, an error message will be activated. In
addition, approx. 5
°C below the limit value, a temperature warning will be activated.