beautypg.com

11 fault-finding, 1 what to do if, Fault-finding – JUMO 706030 LOGOPRINT 500 Printing Recorder Operating Manual User Manual

Page 99: What to do if

background image

99

11 Fault-finding

11.1 What to do if …

Display or printing

“>>>>>>”

- The value is outside the measuring range

(out-of-range)

- The transducer has been connected up incorrectly

- The signal inputs are configured incorrectly

- Probe break

Instead of a value

“ **** ”, “ ±*.*** ”, “ ±**.** ”,
“ ±***.* ”, “ ±****. ”

is displayed or printed

- The value can no longer be represented:

alter the scaling with the setup program,
so that the value can always be represented.

- In the case of the event counter:

reset the event counter using the setup program or
the parameter Configuration level 3

Î

Event counter

No recording

- The

S key was pressed

- “External Stop” was configured, and the corresponding

logic input is closed

- The chart cassette has not been fitted correctly

vSection 9.2 “Removing and replacing the chart cassette”

Caution:
Insert the chart cassette by applying light upwards pressure

- The take-up roll has not properly engaged with the

chart cassette

vSection 9.2.1 “Changing the roll chart”

- The end of the chart paper has been reached

vSection 9.2.1 “Changing the roll chart”
vSection 9.2.2 “Changing the fanfold chart”

- The chart speed has been programmed to 0 mm/h

vSection 4.2 “Table of the configuration parameters”

- The plot status is switched to “OFF”

vSection 4.2 “Table of the configuration parameters”

- The setup connector is still plugged in

Print head doesn‘t write

- The print head has not been inserted properly

vSection 8.3 “Fitting the print head”

- The ink in the print head has been used up