4 Configuration table
End res. Re:
0
≤
Re
≤
4000
Ω
Ra + Rs + Re
≤
4000
Ω
Meas. span
≥
6
Ω
Enter end resistance
Filter:
0.0 — 50.0sec
Enter filter constant
Configuration level 1
➔ Measurement input
Type: voltage
Characteristic:
linear, Pt100, Pt100 JIS,
Pt500, Pt1000, Ni100, L, J,
U, T, K, E, N, S, R, B, X1,
X2
X1 = customer-specific
linearisation 1
X2 = customer-specific
linearisation 2
(with X1 or X2 : followed
immediately by the entry
for the filter parameter)
Unit:
mV, V
Range start:
-9999 to +9999
-10V
≤
range start
<
10V
Enter start of
measurement range
1
Range end:
-9999 to +9999
-10V
<
range end
≤
10V
Meas. span
≥
5mV
Enter end of
measurement range
1
Temperature:
(dimension)
°C, °F
(only for thermocouples
and resistance
thermometers)
Temp. start:
-9999 to +9999
Enter start of temperature
range
1
(only for thermocouples
and resistance
thermometers)
Temp. end:
-9999 to +9999
Measurement span
- Resistance
thermometer
≥
15°C
- Thermocouples
≥
100°C
- S, R, B
≥
500°C
Enter end of temperature
range
1
(only for thermocouples
and resistance
thermometers)
Filter:
0.0 — 50.0sec
Enter filter constant
Configuration level 1
➔ Measurement input
Type: current / shunt
Characteristic:
linear, Pt 100, Pt 100 JIS,
Pt 500, Pt 1000, Ni 100, L,
J, U, T, K, E, N, S, R, B, X1,
X2
X1 = customer-specific
linearisation 1
X2 = customer-specific
linearisation 2
(with X1 or X2 : followed
immediately by the entry
for the filter parameter)
Range start:
-9999 to +9999
-20mA
≤
rge. start
<
20mA
Enter start of measurement
range
1
1. The limits for range start (temp. start) and range end (temp. end) differ
according to the characteristic
Parameter
Value/selection